Specifications |
PH |
PV |
CF |
CN |
|
Voltage |
120/240 Vac |
120/240 Vac |
120/240 Vac a 24/48 Vdc |
120/230 Vac a 24/48 Vdc |
|
Current range |
3–20 A |
1–5 A |
10–60 A |
30 A |
|
DIN mounting |
Yes |
Yes |
Yes b |
No |
|
UL 1283 7th Edition and UL 1449 4th Edition |
Yes |
Yes |
Yes c |
Yes c |
|
Filtering |
Yes |
Yes |
Yes |
No |
|
EMI/RFI filtering attenuation at 100 kHz |
75 dB |
50 dB |
40 dB |
N/A |
|
L to G, L to N and N to G protection modes |
Yes |
Yes |
Yes |
Yes |
|
Peak kA per phase / mode |
60/30 |
40/20 |
80/40 |
80/40 |
|
UL nominal discharge current (In) |
5 kA |
5 kA |
5 kA |
5 kA |
|
UL voltage protection rating (VPR) L–G / L–N d |
330/400 |
330/400 |
500/500 |
500/500 |
|
Short-circuit current rating (SCCR) |
5 kA |
5 kA |
10 kA |
10 kA |
|
Alarm contacts |
Yes |
No |
Yes e |
No |
|
Standard warranty / registered warranty (years) |
10/15 |
10/15 |
5/10 |
5/10 |
|
Communication line protection (UL 497A) |
No |
No |
Yes e |
No |
Call 800-387-2537 or email us at customerservice@etechnologies.com to learn more.
Back